Vertiv Liebert LTS 32A 2U Rack Load Transfer Switch, Hardwired Dual Input, 4x C13 + 4x C19 Outlets
PRODUCT DESCRIPTION
Vertiv Liebert LTS 32 A Load Transfer Switch, Hardwired Input, 4x C13 + 4x C19 (LTS 32A, 02353758) - 2 Years Local Warranty
Dual-Source Redundancy for Single-Corded Equipment
The Vertiv™ Liebert® LTS™ is a two-pole automatic load transfer switch for 220/230 V single-phase racks. It takes two independent AC feeds — typically an A-feed and a B-feed from two UPS systems, or UPS and mains — and supplies its outlets from the main source, switching automatically to the standby source if the main one fails.
As Vertiv points out, usually only high-end servers have dual power supplies. Switches, routers, hubs, entry-level servers and specialised instruments are single-corded, and the LTS lets you put that equipment on two redundant power paths without replacing it.
“First Disconnect, Then Connect” Transfer
The LTS uses a break-before-make control method. If one source fails, the load is moved to the redundant source in under 6 ms typical (11 ms maximum). If a short circuit occurs on the load side, the design stops the fault from being carried across to the standby source, so the second feed stays healthy for the rest of your rack.
Full DSP control handles detection and transfer, and advanced power-off detection lets the unit judge a source failure quickly.
This Model: 32 A, Hard-wired Input, 4 x C13 + 4 x C19
The Liebert LTS 32A (Vertiv part 02353758) is rated 32 A, accepts its two feeds on hard-wired terminals and distributes power on 4 x IEC C13 (10 A each) + 4 x IEC C19 (16 A each). It is a 2U (84 mm) 19-inch rack unit (84 x 430 x 340 mm H x W x D, 5 kg), so it fits in the same rack as the equipment it protects. Remote monitoring is available through an optional SNMP card.
Where It Fits
Vertiv lists computer equipment rooms, internet data centres, telecom and financial data centres, and industrial process control centres as typical applications. In a Singapore server room it is a simple way to give network switches, firewalls and single-PSU servers the same A/B redundancy as your dual-corded kit.
Supplied in Singapore by SourceIT
SourceIT supplies the Vertiv Liebert LTS range with a GST invoice and local support, with a 2-year warranty per the Singapore distributor price book. Unsure which input or outlet mix you need? Email sales@sourceit.com.sg with your two power sources and the equipment you want to protect.
Vertiv Liebert LTS 32 A Datasheet — Technical Specifications
General
| Model | Vertiv Liebert LTS 32 A |
| Vertiv Part Number | 02353758 |
| Series | Vertiv Liebert LTS 10A – 32A (rack load transfer switch) |
| Type | Automatic load transfer switch, 2 poles |
| Form Factor | 19-inch rack, 2U (84 mm) |
| Manufacturer Warranty | 2 years (Singapore distributor price book; Vertiv does not print a warranty term in the LTS brochures) |
| Local Warranty (Singapore) | Included with every unit supplied by SourceIT, with GST invoice |
Input
| Rating | 32 A |
| Input Connectors | Hard-wired (two sources) |
| Input Source | Two ways of input sources |
| Input Mode | 1Φ + N + PE |
| Rated Voltage | 220/230 VAC |
| Voltage Range | 150 – 300 VAC |
| Rated Frequency | 50/60 Hz |
| Frequency Range | Rated frequency ±5 Hz |
| Voltage Distortion | <10% |
Output
| Output Connector Type | C13 & C19 |
| Outlets (Rating & Quantity) | 4 x IEC C13 (10 A each) + 4 x IEC C19 (16 A each) |
| Power Factor | 0.8 – 1.0 lead or lag |
| Overload Capacity | 125% for 30 min (tested at 30 °C) |
| Efficiency (100% linear load) | 99% |
Transfer
| Number of Poles | 2 |
| Automatic Transfer Interval | <6 ms typical, <11 ms maximum |
| Transfer Method | “First disconnect, then connect”, full DSP control |
Communications
| Remote Management | Via optional SNMP card |
Physical & Environmental
| Dimensions (H x W x D) | 84 x 430 x 340 mm |
| Weight | 5 kg |
| Operating Temperature | 0 – 40 °C |
| Storage Temperature | -40 – 70 °C |
| Relative Humidity | 5 – 95%, non-condensing |
| Elevation | 3,000 m |
| Pollution Level | Level II |
Compatibility & Software Support
Power Sources
Connect two independent 220/230 V single-phase sources (for example two UPS units, or a UPS and utility mains). The unit runs the load from the main source and transfers automatically to the standby source on failure, then back when the main source returns.
Inputs and Outlets
This model takes its two feeds on hard-wired terminals and provides 4 x IEC C13 (10 A each) + 4 x IEC C19 (16 A each). The two 32 A feeds are hard-wired and must be installed by a licensed electrician.
Connected Equipment
Single-corded servers, switches, routers, firewalls, storage and instruments on IEC C13/C19 plugs. Keep the total load within the 32 A rating.
Monitoring
Remote management through an optional SNMP card, per Vertiv. Ask SourceIT for the current card part number and price.
Package Contents & Liebert LTS Ordering Information
In the Box
Liebert LTS load transfer switch for 19-inch rack mounting. Vertiv’s LTS brochures do not publish a package-contents list (for example rack ears or input cords) — confirm what you need with us before ordering.
Vertiv Liebert LTS 10A – 32A — Ordering Information
| Model | Part No. | Input | Outlets | Size / Weight |
| Liebert LTS 10A | 02312189 | 2 x IEC 60320 C14 (one per source) | 8 x IEC C13 (10 A each) | 44 x 430 x 250 mm / 4.5 kg |
| Liebert LTS 16A IEC309 | 02312188 | 2 x IEC 60309 (IEC309) — Vertiv “Model 1” | 6 x IEC C13 (10 A each) + 1 x IEC C19 (16 A) | 44 x 430 x 250 mm / 4.5 kg |
| Liebert LTS 16A C20 | 02312186 | 2 x IEC 60320 C20 — Vertiv “Model 2” | 6 x IEC C13 (10 A each) + 1 x IEC C19 (16 A) | 44 x 430 x 250 mm / 4.5 kg |
| Liebert LTS 32A (this listing) | 02353758 | Hard-wired (two sources) | 4 x IEC C13 (10 A each) + 4 x IEC C19 (16 A each) | 84 x 430 x 340 mm / 5 kg |
Datasheet & Downloads
| Vertiv brochure (Asia) | Liebert LTS 10A – 32A Brochure — Asia (PDF) |
| Vertiv brochure (India) | Liebert LTS 10A – 32A Brochure — India (PDF) |
Need a PDF sent directly? Email sales@sourceit.com.sg quoting 02353758.
Frequently Asked Questions — Vertiv Liebert LTS 32 A
What does a load transfer switch do?
It gives single-corded equipment two power sources. The LTS feeds the load from the main source and switches to the standby source automatically if the main one fails, so equipment with only one power supply still benefits from A/B redundancy.
How fast is the transfer?
Vertiv specifies less than 6 ms typical and less than 11 ms maximum, using a break-before-make (“first disconnect, then connect”) method.
Is it a UPS?
No. The LTS has no battery; it switches between two sources that you supply. Pair it with two UPS units (or UPS plus mains) for full protection.
What happens if a connected device shorts?
Vertiv states the LTS is designed so a short circuit is not carried over to the standby source, protecting the second feed and the rest of the rack.
Can it be monitored remotely?
Yes, through an optional SNMP card.
What warranty do I get?
2 years, per the Singapore distributor price book, supplied by SourceIT with a GST invoice.