Waste Heat in the Tropics: Can a Singapore Data Centre Reuse Its Heat?
Sustainability reports from data centre operators love one story in particular. A facility in Scandinavia pipes its waste heat into the local network and warms thousands of homes. It is a good story, and it is true.
It is also a story about a cold country. Singapore has the heat and nobody who wants it. So what, if anything, can heat reuse mean here?
Why the northern model does not travel
District heating is the most common use for data centre waste heat, and its viability has been shown in many studies. But it rests on two conditions.
| Condition | ❄️ Northern Europe | 🌴 Singapore |
|---|---|---|
| Someone needs heat | Yes Homes and offices, for much of the year | Hardly Buildings need cooling, all year |
| A network to carry it | Yes District heating pipes already exist | No The district networks here carry chilled water |
| The heat is hot enough | Not by itself Heat pumps are used to raise it | Same problem |
Sources: Towards a Systematic Survey for Carbon Neutral Data Centers, Singapore Institute of Technology on district cooling. The Singapore column is our own assessment.
The quality problem
The third row matters everywhere. Data centre heat is what engineers call low-grade. One study puts the air leaving a data centre at only 30 to 40 °C, far cooler than most industrial waste heat. District heating networks run at around 90 °C on the supply side, which is why even in cold countries a heat pump is usually needed to lift the temperature.
In Singapore the gap is more awkward still. IEEE Spectrum, reporting on research here, notes daily temperatures of 31 to 33 °C with very high humidity. Heat at 35 °C is not much of a resource when the air outside is 32 °C.
Sources: Frontiers in Sustainability: a material social view on data centre waste heat, IEEE Spectrum: cooling ideas for tropical data centres
Where liquid cooling changes the picture
This is the one place AI hardware helps. Liquid-cooled systems carry heat away in water that is much warmer than exhaust air. A data centre developer quoted in AI Magazine put it simply: capturing waste heat gets much easier with liquid cooling, because running the water warmer gives better-quality heat.
Warmer water opens options that 35 °C air never could. It does not create a customer for the heat, but it makes the heat worth offering.
Source: AI Magazine, November 2024
What reuse could look like in the tropics
| Idea | How it works | Tropical fit |
|---|---|---|
| ❄️ Heat-driven cooling | Absorption chillers use heat, not electricity, to produce chilled water | Most promising Cooling is what the region needs |
| 🌬️ Drying air | Heat regenerates the desiccant materials used to remove humidity | Promising Under research in Singapore |
| 🌾 Industrial drying | Low-temperature heat used to dry goods or materials | Site-specific Needs a neighbour who wants it |
| 🚿 Hot water | Pre-heating water for hotels, hospitals, laundries or pools | Site-specific Small demand next to the supply |
| 🏠 District heating | Piping heat to homes and offices | No |
Sources: Data Center Dynamics: building energy-efficient data centres in the tropics, report on the Sustainable Tropical Data Centre Testbed, Frontiers in Sustainability. The "tropical fit" column is our own judgement, not a published rating.
The first row is the interesting one. Turning waste heat into cooling is the tropical equivalent of district heating: it converts something you have too much of into the thing everyone nearby wants. It appears in designs for facilities that generate their own power, where the generator's heat drives absorption chillers. Whether the lower-temperature heat from servers alone can do this economically is a harder question, and it is one of the things researchers here are working on.
Singapore has built a dedicated facility for exactly this kind of problem. The Sustainable Tropical Data Centre Testbed at the National University of Singapore covers 770 square metres and brings together the two main universities, government agencies and industry partners to test cooling approaches for hot, humid climates.
The uncomfortable conclusion
For most Singapore facilities today, heat reuse is a research topic, not a procurement option. An operator who lists it as a current benefit should be asked who is using the heat, how much of it, and for how many hours a year.
That is not a reason for cynicism about sustainability here. It is a reason to look at the right measures. In the tropics the larger gains come from making less waste in the first place:
- Efficient cooling. Singapore's Green Data Centre Roadmap is widely cited as setting a power usage effectiveness target of 1.3 or better.
- Warmer operating temperatures. Liquid cooling lets systems run with warmer water, which cuts the energy spent on chilling.
- Water discipline. See AI Rack Water Use in the Tropics.
- Useful work per watt. See Tokens per Watt Explained.
As one industry analysis put it, improving data centre efficiency in the tropics is not impossible, but it is harder and the gains are smaller than in temperate climates. Honest sustainability claims in this region start from that sentence.
Source for the roadmap target: presentation by Assoc Prof Poh Seng Lee, National University of Singapore. Check IMDA's published roadmap for the authoritative wording.
Three questions for a data centre that claims heat reuse
- Who receives the heat, and under what agreement?
- What share of the facility's total heat is reused across a full year?
- Is the figure measured, or is it a design estimate?